The following features come standard on Ultra XS Paint Mix Rooms:
| 4-inch spill containment |
| White pre-coated galvanized steel |
| Single-skin panels |
| Personnel door with observation window |
| Exhaust blower with 1/2 hp motor (120V, 1-phase) |
| Light switch and fan disconnect |
| 3-by-5-foot PIG Grippy Mix Room Mat |
The following options can be added to Ultra XS Paint Mix Rooms:
| Pressurizing blower with 1/2 hp motor (120V, 1-phase) |
| Door cover (required to connect mix room to booth) |
| Observation window |
| Vestibule |
| Additional access door |
| Mix room heater |
| Exhaust stack kit |
| Rotating Booth Access Turntable |
| Control panel |
GFS products are designed and manufactured to meet the applicable requirements of various industry-recognized codes and standards.
- Reference NFPA 33 and Chapter 24 of the International Fire Code (IFC) for spray applications using flammable and combustible materials
- Reference NFPA 86 and Chapter 30 of the IFC for curing and drying applications
- Many components and product lines are ETL and ETL-C (cETLus) listed. The cETLus mark is proof of compliance with North American safety standards, including UL, NFPA, CSA and more
- A UL or CUL (cULus) listing verifies that Underwriters Laboratories has tested GFS’ product and determined that it meets their stringent safety and performance requirements
Please be aware that local requirements may vary from national codes. GFS recommends consulting with your local authority before purchasing paint booths or other finishing equipment.
GFS engineers regularly contribute to the advancement of codes and standards that affect the industries that we work in. Several of our engineers serve on various NFPA Technical Committees responsible for key finishing industry standards.
SAFE STORAGE & USE GUIDELINES
The amount of flammable or combustible liquid stored in paint mix rooms must be within the following limits, per NFPA 33:
- Paint mix rooms within 6 feet of the spray area may contain up to 2 gallons per square foot of enclosure floor area, but the combined quantities of liquids in the spray area and mix room shall not exceed 120 gallons
- Up to 60 gallons may be stored in the spray area
- Paint mix rooms farther than 6 feet from the spray area may contain up to 2 gallons per square foot of enclosure floor area, but shall not exceed 300 gallons
- If more than one paint mix room is installed, the total quantity of liquids shall not exceed the amounts outlined above
- Additional limits may be applicable based upon the amount of flammable or combustible liquids present elsewhere in the building